Clearesult, the entity in charge of the 80 Plus certifications that verifies the efficiency of the power supplies, has published a new level within this scale that is placed above the 80 Plus Titanium and 80 Plus Platinum.
80 Plus Ruby It is the new efficiency level for food sources oriented to systems Data center with redundant sources. To fulfill this new level of efficiency, server feeding sources must achieve an impressive efficiency of 96.5% of the energy converted when they are 50% load with a voltage of 230 V. With that voltage, the minimum efficiency required is 90% and 91% for 5% and 10% loads respectively. With 95% for 20% and 92% for 100% of the load.
80 Plus Ruby only applies to sources that operate at 230V, or models of 277V / 480V AC and 380V DCand in all cases of Redundant type. In cases of 277V / 480V and 380V, the sources must offer an efficiency of 90% to 5% load, 91% to 10% load, 95% to 20% load and 96.5% for 50%. In the case of 100% load, the minimal efficiency required is 92%.
The reason for the existence of 80 Plus Ruby for data centers sources And servers comes from the increase in demand for this type of systems, especially because of the AI rise along with other services. Data centers are expected to consume 0.4% of the US electricity, but forecasts point to excessive growth that will reach between 6.7% and 12% in just 3 years, by 2028.
Specifications of different efficiency levels 80 plus
| 80 Plus Certification | 230V eu internal, not redundant | 230V internal redundant | |||||||
|---|---|---|---|---|---|---|---|---|---|
| % load | 10% | 20% | 50% | 100% | 5% | 10% | 20% | 50% | 100% |
| 80 plus | – | 82% | 85% PFC ≥ 0.90 | 82% | – | – | |||
| 80 Plus Bronze | – | 85% | 88% PFC ≥ 0.90 | 85% | – | – | 81% | 85% PFC ≥ 0.90 | 81% |
| 80 Plus Silver | – | 87% | 90% PFC ≥ 0.90 | 87% | – | – | 85% | 89% PFC ≥ 0.90 | 85% |
| 80 Plus Gold | – | 90% | 92% PFC ≥ 0.90 | 89% | – | – | 88% | 92% PFC ≥ 0.90 | 88% |
| 80 Plus Platinum | – | 92% | 94% PFC ≥ 0.95 | 90% | – | – | 90% | 94% PFC ≥ 0.95 | 91% |
| 80 Plus Titanium | 90% | 94% PFC ≥ 0.95 | 96% | 91% | – | 90% | 94% PFC ≥ 0.95 | 96% | 91% |
| 80 Plus Ruby | – | – | – | – | 90% PFC ≥ 0.90 | 91% PFC ≥ 0.90 | 95% PFC ≥ 0.96 | 96.5% PFC ≥ 0.96 | 92% PFC ≥ 0.96 |
| 80 Plus Certification | 277V / 480V internal redundant | 380V internal redundant | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| % load | 5% | 10% | 20% | 50% | 100% | 5% | 10% | 20% | 50% | 100% |
| 80 plus | ||||||||||
| 80 Plus Bronze | 80% | 82% | 85% PFC ≥ 0.90 | 82% | 80% | 82% | 85% | 82% | ||
| 80 Plus Silver | 82% | 85% | 89% PFC ≥ 0.90 | 85% | 82% | 85% | 89% | 85% | ||
| 80 Plus Gold | 85% | 88% | 92% PFC ≥ 0.90 | 88% | 85% | 88% | 92% | 88% | ||
| 80 Plus Platinum | 88% | 90% | 94% PFC ≥ 0.95 | 91% | 88% | 90% | 94% | 91% | ||
| 80 Plus Titanium | 90% | 94% PFC ≥ 0.95 | 96% | 91% | 90% | 94% | 96% | 91% | ||
| 80 Plus Ruby | 90% PFC ≥ 0.90 | 91% PFC ≥ 0.90 | 95% PFC ≥ 0.96 | 96.5% PFC ≥ 0.96 | 92% PFC ≥ 0.96 | 90% | 91% | 95% | 96.5% | 92% |